The acoustic waves caused by partial discharges inside a dielectric can be detected by sensors of acoustic emissions (EA) and analyzed in the time domain. The experimental results that are presented, demonstrate the capability of online detection of these sensors, in the vicinity of a cable, splice or terminal accessory. The EA sensors are immune to electromagnetic interference, are a non-destructive detection method and guarantee galvanic decoupling from the voltage network; This technique of detection of partial discharges can be applied as a test method for preventive or predictive maintenance (maintenance based on the condition), in equipment or installations of medium and high voltage in service and represents an alternative to electrical detection systems, conventional or not, which continue to be based on the detection of current pulses.
Las ondas acústicas provocadas por las descargas parciales en el interior de un dieléctrico pueden ser detectadas por sensores de emisiones acústicas (EA) y analizadas en el dominio del tiempo. Los resultados experimentales que se presentan, evidencia la capacidad de detección en línea de estos sensores, en el entorno próximo a un accesorio de cable, empalme o terminal. Los sensores EA son inmunes a las interferencia electromagnéticas, son un método de detección no destructivo y garantizan desacople galvánico respecto a la red de tensión; esta técnica de detección de descargas parciales puede ser aplicada como método de prueba para mantenimiento preventivo o predictivo (mantenimiento basado en la condición), en equipos o instalaciones de media y alta tensión en servicio y representa una alternativa a los sistemas eléctricos de detección, convencionales o no, que continúan basándose en la detección del impulsos de corriente.